Artel Group Artel Group
Artel Group
Products
Fan Coil - RCLW18RL

RCL-RC


RX threephase
Remote control

comunità europrea

pulsante details

COOLING

Conditions: room air temp. 27°C (dry bulb) - 19°C (wet bulb); inlet water temp. 7 °C, high fan speed

    RCLW18RL
CAPACITY W 3500
Frig/h 3010
BTU/h 11935
SENSIBLE CAPACITY W 2520
Frig/h 2167
BTU/h 8593
WATER PRESSURE DROPS kPa 24,04
mca 2,45

HEATING

Conditions: air temp. 20°C(D.B.); inlet water temp. 50°C; high fan speed.

CAPACITY W 5300
Frig/h 4558
BTU/h 18073
WATER PRESSURE DROPS kPa 20,40
mca 2,08

HEATING

conditions: air temp. 20°C(D.B.); inlet water temp. 70°C; high fan speed.

CAPACITY W 8833
kCal/h 7597
BTU/h 30122
WATER FLOW RATE L/h 720

INLET+OUTLET PIPE CONNECTION

DIAMETER in 3/4

DRAIN CONNECTION

INSIDE DIAMETER mm 24

FAN MOTOR

Voltage-Frequency-Phases V-Hz-n 230-50-1
Power input W 83
Running Current A 0,36
Nominal air flow rate m³/h 680

NOISE LEVEL*

NOISE LEVEL dB(A) 48

DIMENSIONS AND WEIGHTS

Housing    
LENGTH mm 570
HEIGHT mm 570
DEPTH mm 310
Front Panel    
LENGTH mm 720
HEIGHT mm 720
DEPTH mm 40
NET WEIGHT kg 24,5








back

*Measured 1 m from the unit in the acoustic room.

The products on this page are intended exclusively for markets outside Italy.

The information is indicative and could be subject to variations without notice.


Autore: Artel SpA/ls
Artel spa
Viale dell'Artigianato, 34
36030 S.Vito di Leguzzano (Vicenza) Italy
Tel. +39 0445/595000 (20 linee I.S.D.N.)
Fax +39 0445/595900 - Export +39 0445/595959
P.IVA IT 01323800241
export@artelgroup.com