Artel Group Artel Group
Artel Group
Products
Fan Coil - RCLW24RL

RCL-RC


RX threephase
Remote control

comunità europea

pulsante details

COOLING

Conditions: room air temp. 27°C (dry bulb) - 19°C (wet bulb); inlet water temp. 7 °C, high fan speed

    RCLW24RL
CAPACITY W 4600
Frig/h 3956
BTU/h 15686
SENSIBLE CAPACITY W 3312
Frig/h 2848
BTU/h 11294
WATER PRESSURE DROPS kPa 31,66
mca 3,23

HEATING

Conditions: air temp. 20°C(D.B.); inlet water temp. 50°C; high fan speed.

CAPACITY W 6300
Frig/h 5418
BTU/h 21483
WATER PRESSURE DROPS kPa 26,80
mca 2,73

HEATING

conditions: air temp. 20°C(D.B.); inlet water temp. 70°C; high fan speed.

CAPACITY W 10500
kCal/h 9030
BTU/h 35805
WATER FLOW RATE L/h 840

INLET+OUTLET PIPE CONNECTION

DIAMETER in 3/4

DRAIN CONNECTION

INSIDE DIAMETER mm 24

FAN MOTOR

Voltage-Frequency-Phases V-Hz-n 230-50-1
Power input W 94
Running Current A 0,37
Nominal air flow rate m³/h 815

NOISE LEVEL*

NOISE LEVEL dB(A) 53

DIMENSIONS AND WEIGHTS

Housing    
LENGTH mm 570
HEIGHT mm 570
DEPTH mm 310
Front Panel    
LENGTH mm 720
HEIGHT mm 720
DEPTH mm 40
NET WEIGHT kg 24,5








back

*Measured 1 m from the unit in the acoustic room.

The products on this page are intended exclusively for markets outside Italy.

The information is indicative and could be subject to variations without notice.


Autore: Artel SpA/ls
Artel spa
Viale dell'Artigianato, 34
36030 S.Vito di Leguzzano (Vicenza) Italy
Tel. +39 0445/595000 (20 linee I.S.D.N.)
Fax +39 0445/595900 - Export +39 0445/595959
P.IVA IT 01323800241
export@artelgroup.com